Inverter 10-24KW Energy Fronius

Description

HIGHLIGHTS

Updating..

TYPE10.0-3 208/24012.0-3 208/240
Input (DC)
Max. permitted PV power15.00 kW18.00 kW
Max. usable input current (MPPT 1/MPPT 2)25.0 A / 16.5 A25.0 A / 16.5 A
Max. usable input current total (MPPT 1 + MPPT 2)41.5 A41.5 A
Max. admissible input current (MPPT 1/MPPT 2)37.5 A / 24.8 A
Max. admissible input current total (MPPT 1 + MPPT 262.2 A62.2 A
Integrated DC string fuse holders
Must be specified when ordering
NoneNone
MPP voltage range300 – 500 V300 – 500 V
Operating voltage range200 – 600 V200 – 600 V
Max. input voltage600 V600 V
Nominal input voltage 208 V350 V350 V
240 V370 V370 V
480 VN/AN/A
Admissible conductor size DCAWG 14 – AWG 6 copper direct, AWG 6 aluminium direct, AWG 4 copper or aluminium with input combinerAWG 14 – AWG 6 copper direct, AWG 6 aluminium direct, AWG 4 copper or aluminium with input combiner
Number of MPPT22
OUTPUT DATA
Max. output power 208 V9,995 VA11,995 VA
240 V9,995 VA11,995 VA
480 VN/AN/A
Max. output fault current / Duration43.1 A RMS / 158.4 ms43.1 A RMS / 158.4 ms
Max. continuous output current 208 V27.7 A33.3 A
240 V24.0 A28.9 A
480 VN/AN/A
Recommended OCPD/AC breaker size 208 V35 A45 A
240 V30 A40 A
480 VN/AN/A
Max. efficiency97.00%97.00%
CEC efficiency 208 V96.50%96.50%
240 V96.50%96.50%
480 VN/AN/A
Admissible conductor size ACAWG 14 – AWG 6
Grid connection208 / 240 V208 / 240 V
Frequency60 Hz60 Hz
Total harmonic distortion< 1.75 %< 1.75 %
Power factor0 – 1 ind./cap0 – 1 ind./cap
GENERAL DATASTANDARD WITH ALL FRONIUS SYMO MODELSSTANDARD WITH ALL FRONIUS SYMO MODELS
Dimensions (width x height x depth)20.1 x 28.5 x 8.9 in. / 51.1 x 72.4 x 22.6 cm20.1 x 28.5 x 8.9 in. / 51.1 x 72.4 x 22.6 cm
Degree of protectionNEMA 4XNEMA 4X
Night time consumption< 1 W< 1 W
Inverter topologyTransformerlessTransformerless
CoolingVariable speed fanVariable speed fan
InstallationIndoor and outdoor installationIndoor and outdoor installation
Ambient operating temperature range-40 F to 140 F (-40 to 60 C)-40 F to 140 F (-40 to 60 C)
Permitted humidity0 – 100 % (non-condensing)0 – 100 % (non-condensing)
DC connection terminals6 x DC+ and 6 x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminum (solid / stranded)6 x DC+ and 6 x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminum (solid / stranded)
AC connection terminalsScrew terminals 14-6 AWGScrew terminals 14-6 AWG
Certificates and compliance with standards
(Except Symo 15.0 208 V)
UL 1741-2010, UL1998 (for functions: AFCI and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2008, ANSI/IEEE C62.41,
FCC Part 15 A & B, NEC Article 690, C22. 2 No. 107.1-01 ( September 2001), UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
UL 1741-2010, UL1998 (for functions: AFCI and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2008, ANSI/IEEE C62.41,
FCC Part 15 A & B, NEC Article 690, C22. 2 No. 107.1-01 ( September 2001), UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
Certificates and compliance with standards
(Symo 15.0 208 V)
UL 1741-2015, UL1998 (for functions: AFCI, RCMU and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2003, ANSI/IEEE C62.41,
FCC Part 15 A & B, NEC 2014 Article 690, C22. 2 No. 107.1-01 (September 2001) , UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
UL 1741-2015, UL1998 (for functions: AFCI, RCMU and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2003, ANSI/IEEE C62.41,
FCC Part 15 A & B, NEC 2014 Article 690, C22. 2 No. 107.1-01 (September 2001) , UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
PROTECTIVE DEVICESSTANDARD WITH ALL FRONIUS SYMO MODELSSTANDARD WITH ALL FRONIUS SYMO MODELS
AFCI & 2014 NEC CompliantYesYes
DC disconnectYesYes
DC reverse polarity protectionYesYes
Ground Fault Protection with Isolation
Monitor Interrupter
YesYes
INTERFACES /AVAILABILITYAVAILABLE WITH ALL FRONIUS SYMO MODELSAVAILABLE WITH ALL FRONIUS SYMO MODELS
USB (A socket) StandardDatalogging and inverter update via USBDatalogging and inverter update via USB
2 x RS422 (RJ45 socket) StandardFronius Solar Net, interface protocolFronius Solar Net, interface protocol
Wi-Fi/Ethernet/Serial/ Datalogger and
webserver Optional
Wireless standard 802.11 b/g/n / Fronius Solar.web, SunSpec Modbus TCP, JSON / SunSpec Modbus RTUWireless standard 802.11 b/g/n / Fronius Solar.web, SunSpec Modbus TCP, JSON / SunSpec Modbus RTU
6 inputs and 4 digital I/Os OptionalLoad management; signaling, multipurpose I/OLoad management; signaling, multipurpose I/O

 


TYPE10.0-3 48012.5-3 480
Input (DC)
Max. permitted PV power15.00 kW18.75 kW
Max. usable input current (MPPT 1/MPPT 2)25.0 A / 16.5 A25.0 A / 16.5 A
Max. usable input current total (MPPT 1 + MPPT 2)41.5 A41.5 A
Max. admissible input current (MPPT 1/MPPT 2)
Max. admissible input current total (MPPT 1 + MPPT 262.2 A62.2 A
Integrated DC string fuse holders
Must be specified when ordering
NoneNone
MPP voltage range300 – 800 V350 – 800 V
Operating voltage range200 – 600 V200 – 600 V
Max. input voltage1,000 V1,000 V
Nominal input voltage 208 VN/AN/A
240 VN/AN/A
480 V675 V685 V
Admissible conductor size DCAWG 14 – AWG 6 copper direct, AWG 6 aluminium direct, AWG 4 copper or aluminium with input combinerAWG 14 – AWG 6 copper direct, AWG 6 aluminium direct, AWG 4 copper or aluminium with input combiner
Number of MPPT22
OUTPUT DATA
Max. output power 208 VN/AN/A
240 VN/AN/A
480 V9,995 VA12,495 VA
Max. output fault current / Duration43.1 A RMS / 158.4 ms43.1 A RMS / 158.4 ms
Max. continuous output current 208 VN/AN/A
240 VN/AN/A
480 V12.0 A15.0 A
Recommended OCPD/AC breaker size 208 VN/AN/A
240 VN/AN/A
480 V15 A20 A
Max. efficiency98.10%98.10%
CEC efficiency 208 VN/AN/A
240 VN/AN/A
480 V96.50%97.00%
Admissible conductor size AC
Grid connection480 V Delta +N**480 V Delta +N**
Frequency60 Hz60 Hz
Total harmonic distortion< 1.75 %< 1.75 %
Power factor0 – 1 ind./cap0 – 1 ind./cap
GENERAL DATASTANDARD WITH ALL FRONIUS SYMO MODELSSTANDARD WITH ALL FRONIUS SYMO MODELS
Dimensions (width x height x depth)20.1 x 28.5 x 8.9 in. / 51.1 x 72.4 x 22.6 cm20.1 x 28.5 x 8.9 in. / 51.1 x 72.4 x 22.6 cm
Degree of protectionNEMA 4XNEMA 4X
Night time consumption< 1 W< 1 W
Inverter topologyTransformerlessTransformerless
CoolingVariable speed fanVariable speed fan
InstallationIndoor and outdoor installationIndoor and outdoor installation
Ambient operating temperature range-40 F to 140 F (-40 to 60 C)-40 F to 140 F (-40 to 60 C)
Permitted humidity0 – 100 % (non-condensing)0 – 100 % (non-condensing)
DC connection terminals6 x DC+ and 6 x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminum (solid / stranded)6 x DC+ and 6 x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminum (solid / stranded)
AC connection terminalsScrew terminals 14-6 AWGScrew terminals 14-6 AWG
Certificates and compliance with standards
(Except Symo 15.0 208 V)
UL 1741-2010, UL1998 (for functions: AFCI and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2008, ANSI/IEEE C62.41,
FCC Part 15 A & B, NEC Article 690, C22. 2 No. 107.1-01 ( September 2001), UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
UL 1741-2010, UL1998 (for functions: AFCI and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2008, ANSI/IEEE C62.41,
FCC Part 15 A & B, NEC Article 690, C22. 2 No. 107.1-01 ( September 2001), UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
Certificates and compliance with standards
(Symo 15.0 208 V)
UL 1741-2015, UL1998 (for functions: AFCI, RCMU and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2003, ANSI/IEEE C62.41,
FCC Part 15 A & B, NEC 2014 Article 690, C22. 2 No. 107.1-01 (September 2001) , UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
UL 1741-2015, UL1998 (for functions: AFCI, RCMU and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2003, ANSI/IEEE C62.41,
FCC Part 15 A & B, NEC 2014 Article 690, C22. 2 No. 107.1-01 (September 2001) , UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
PROTECTIVE DEVICESSTANDARD WITH ALL FRONIUS SYMO MODELSSTANDARD WITH ALL FRONIUS SYMO MODELS
AFCI & 2014 NEC CompliantYesYes
DC disconnectYesYes
DC reverse polarity protectionYesYes
Ground Fault Protection with Isolation
Monitor Interrupter
YesYes
INTERFACES /AVAILABILITYAVAILABLE WITH ALL FRONIUS SYMO MODELSAVAILABLE WITH ALL FRONIUS SYMO MODELS
USB (A socket) StandardDatalogging and inverter update via USBDatalogging and inverter update via USB
2 x RS422 (RJ45 socket) StandardFronius Solar Net, interface protocolFronius Solar Net, interface protocol
Wi-Fi/Ethernet/Serial/ Datalogger and
webserver Optional
Wireless standard 802.11 b/g/n / Fronius Solar.web, SunSpec Modbus TCP, JSON / SunSpec Modbus RTUWireless standard 802.11 b/g/n / Fronius Solar.web, SunSpec Modbus TCP, JSON / SunSpec Modbus RTU
6 inputs and 4 digital I/Os OptionalLoad management; signaling, multipurpose I/OLoad management; signaling, multipurpose I/O

TYPE15.0-3 20815.0-3 480
Input (DC)
Max. permitted PV power22.50 kW22.50 kW
Max. usable input current (MPPT 1/MPPT 2)25.0 A / 16.5 A33.0 A / 25.0 A
Max. usable input current total (MPPT 1 + MPPT 2)41.5 A51 A
Max. admissible input current (MPPT 1/MPPT 2)75.0 A49.5 A / 37.5 A
Max. admissible input current total (MPPT 1 + MPPT 262.2 A76.5 A
Integrated DC string fuse holders
Must be specified when ordering
Integrated: 6- and 6+Optional: 6- and 6+
MPP voltage range325 – 850 V350 – 800 V
Operating voltage range325 – 1,000 V200 – 1,000 V
Max. input voltage1,000 V1,000 V
Nominal input voltage 208 V325 VN/A
240 VN/AN/A
480 VN/A685 V
Admissible conductor size DCAWG 14 – AWG 6 copper direct, AWG 6 aluminium direct, AWG 4 copper or aluminium with input combinerAWG 14 – AWG 6 copper direct, AWG 6 aluminium direct, AWG 4 copper or aluminium with input combiner
Number of MPPT12
OUTPUT DATA
Max. output power 208 V15,000 VAN/A
240 VN/AN/A
480 VN/A14,995 VA
Max. output fault current / Duration67.7 A RMS / 153.0 ms30.9 A RMS / 150.4 ms
Max. continuous output current 208 V41.6 AN/A
240 VN/AN/A
480 VN/A18.0 A
Recommended OCPD/AC breaker size 208 V60 AN/A
240 VN/AN/A
480 VN/A25 A
Max. efficiency97.30%98.00%
CEC efficiency 208 V96.50%N/A
240 VN/AN/A
480 VN/A97.00%
Admissible conductor size ACAWG 14 – AWG 6
Grid connection208 V480 V Delta +N**
Frequency60 Hz60 Hz
Total harmonic distortion< 3.5%< 1.75 %
Power factor0 – 1 ind./cap0 – 1 ind./cap.
GENERAL DATASTANDARD WITH ALL FRONIUS SYMO MODELSSTANDARD WITH ALL FRONIUS SYMO MODELS
Dimensions (width x height x depth)20.1 x 28.5 x 8.9 in. / 51.1 x 72.4 x 22.6 cm20.1 x 28.5 x 8.9 in. / 51.1 x 72.4 x 22.6 cm
Degree of protectionNEMA 4XNEMA 4X
Night time consumption< 1 W< 1 W
Inverter topologyTransformerlessTransformerless
CoolingVariable speed fanVariable speed fan
InstallationIndoor and outdoor installationIndoor and outdoor installation
Ambient operating temperature range-40 F to 140 F (-40 to 60 C)-40 F to 140 F (-40 to 60 C)
Permitted humidity0 – 100 % (non-condensing)0 – 100 % (non-condensing)
DC connection terminals6 x DC+ and 6 x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminum (solid / stranded)6 x DC+ and 6 x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminum (solid / stranded)
AC connection terminalsScrew terminals 14-6 AWGScrew terminals 14-6 AWG
Certificates and compliance with standards
(Except Symo 15.0 208 V)
UL 1741-2010, UL1998 (for functions: AFCI and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2008, ANSI/IEEE C62.41,
FCC Part 15 A & B, NEC Article 690, C22. 2 No. 107.1-01 ( September 2001), UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
UL 1741-2010, UL1998 (for functions: AFCI and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2008, ANSI/IEEE C62.41,
FCC Part 15 A & B, NEC Article 690, C22. 2 No. 107.1-01 ( September 2001), UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
Certificates and compliance with standards
(Symo 15.0 208 V)
UL 1741-2015, UL1998 (for functions: AFCI, RCMU and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2003, ANSI/IEEE C62.41,
FCC Part 15 A & B, NEC 2014 Article 690, C22. 2 No. 107.1-01 (September 2001) , UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
UL 1741-2015, UL1998 (for functions: AFCI, RCMU and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2003, ANSI/IEEE C62.41,
FCC Part 15 A & B, NEC 2014 Article 690, C22. 2 No. 107.1-01 (September 2001) , UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
PROTECTIVE DEVICESSTANDARD WITH ALL FRONIUS SYMO MODELSSTANDARD WITH ALL FRONIUS SYMO MODELS
AFCI & 2014 NEC CompliantYesYes
DC disconnectYesYes
DC reverse polarity protectionYesYes
Ground Fault Protection with Isolation
Monitor Interrupter
YesYes
INTERFACES /AVAILABILITYAVAILABLE WITH ALL FRONIUS SYMO MODELSAVAILABLE WITH ALL FRONIUS SYMO MODELS
USB (A socket) StandardDatalogging and inverter update via USBDatalogging and inverter update via USB
2 x RS422 (RJ45 socket) StandardFronius Solar Net, interface protocolFronius Solar Net, interface protocol
Wi-Fi/Ethernet/Serial/ Datalogger and
webserver Optional
Wireless standard 802.11 b/g/n / Fronius Solar.web, SunSpec Modbus TCP, JSON / SunSpec Modbus RTUWireless standard 802.11 b/g/n / Fronius Solar.web, SunSpec Modbus TCP, JSON / SunSpec Modbus RTU
6 inputs and 4 digital I/Os OptionalLoad management; signaling, multipurpose I/OLoad management; signaling, multipurpose I/O

TYPE17.5-3 48020.0-3 480
Input (DC)
Max. permitted PV power26.25 kW30.00 kW
Max. usable input current (MPPT 1/MPPT 2)33.0 A / 25.0 A33.0 A / 25.0 A
Max. usable input current total (MPPT 1 + MPPT 2)51 A51 A
Max. admissible input current (MPPT 1/MPPT 2)49.5 A / 37.5 A49.5 A / 37.5 A
Max. admissible input current total (MPPT 1 + MPPT 276.5 A76.5 A
Integrated DC string fuse holders
Must be specified when ordering
Optional: 6- and 6+Optional: 6- and 6+
MPP voltage range400 – 800 V450 – 800 V
Operating voltage range200 – 1,000 V200 – 1,000 V
Max. input voltage1,000 V1,000 V
Nominal input voltage 208 VN/AN/A
240 VN/AN/A
480 V685 V710 V
Admissible conductor size DCAWG 14 – AWG 6 copper direct, AWG 6 aluminium direct, AWG 4 copper or aluminium with input combinerAWG 14 – AWG 6 copper direct, AWG 6 aluminium direct, AWG 4 copper or aluminium with input combiner
Number of MPPT22
OUTPUT DATA
Max. output power 208 VN/AN/A
240 VN/AN/A
480 V17,495 VA19,995 VA
Max. output fault current / Duration30.9 A RMS / 150.4 ms30.9 A RMS / 150.4 ms
Max. continuous output current 208 VN/AN/A
240 VN/AN/A
480 V21.0 A24.0 A
Recommended OCPD/AC breaker size 208 VN/AN/A
240 VN/AN/A
480 V30 A30 A
Max. efficiency98.00%98.00%
CEC efficiency 208 VN/AN/A
240 VN/AN/A
480 V97.50%97.50%
Admissible conductor size ACAWG 14 – AWG 6AWG 14 – AWG 6
Grid connection480 V Delta +N**480 V Delta +N**
Frequency60 Hz60 Hz
Total harmonic distortion< 1.75 %< 1.75 %
Power factor0 – 1 ind./cap.0 – 1 ind./cap.
GENERAL DATASTANDARD WITH ALL FRONIUS SYMO MODELSSTANDARD WITH ALL FRONIUS SYMO MODELS
Dimensions (width x height x depth)20.1 x 28.5 x 8.9 in. / 51.1 x 72.4 x 22.6 cm20.1 x 28.5 x 8.9 in. / 51.1 x 72.4 x 22.6 cm
Degree of protectionNEMA 4XNEMA 4X
Night time consumption< 1 W< 1 W
Inverter topologyTransformerlessTransformerless
CoolingVariable speed fanVariable speed fan
InstallationIndoor and outdoor installationIndoor and outdoor installation
Ambient operating temperature range-40 F to 140 F (-40 to 60 C)-40 F to 140 F (-40 to 60 C)
Permitted humidity0 – 100 % (non-condensing)0 – 100 % (non-condensing)
DC connection terminals6 x DC+ and 6 x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminum (solid / stranded)6 x DC+ and 6 x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminum (solid / stranded)
AC connection terminalsScrew terminals 14-6 AWGScrew terminals 14-6 AWG
Certificates and compliance with standards
(Except Symo 15.0 208 V)
UL 1741-2010, UL1998 (for functions: AFCI and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2008, ANSI/IEEE C62.41,
FCC Part 15 A & B, NEC Article 690, C22. 2 No. 107.1-01 ( September 2001), UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
UL 1741-2010, UL1998 (for functions: AFCI and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2008, ANSI/IEEE C62.41,
FCC Part 15 A & B, NEC Article 690, C22. 2 No. 107.1-01 ( September 2001), UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
Certificates and compliance with standards
(Symo 15.0 208 V)
UL 1741-2015, UL1998 (for functions: AFCI, RCMU and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2003, ANSI/IEEE C62.41,
FCC Part 15 A & B, NEC 2014 Article 690, C22. 2 No. 107.1-01 (September 2001) , UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
UL 1741-2015, UL1998 (for functions: AFCI, RCMU and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2003, ANSI/IEEE C62.41,
FCC Part 15 A & B, NEC 2014 Article 690, C22. 2 No. 107.1-01 (September 2001) , UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
PROTECTIVE DEVICESSTANDARD WITH ALL FRONIUS SYMO MODELSSTANDARD WITH ALL FRONIUS SYMO MODELS
AFCI & 2014 NEC CompliantYesYes
DC disconnectYesYes
DC reverse polarity protectionYesYes
Ground Fault Protection with Isolation
Monitor Interrupter
YesYes
INTERFACES /AVAILABILITYAVAILABLE WITH ALL FRONIUS SYMO MODELSAVAILABLE WITH ALL FRONIUS SYMO MODELS
USB (A socket) StandardDatalogging and inverter update via USBDatalogging and inverter update via USB
2 x RS422 (RJ45 socket) StandardFronius Solar Net, interface protocolFronius Solar Net, interface protocol
Wi-Fi/Ethernet/Serial/ Datalogger and
webserver Optional
Wireless standard 802.11 b/g/n / Fronius Solar.web, SunSpec Modbus TCP, JSON / SunSpec Modbus RTUWireless standard 802.11 b/g/n / Fronius Solar.web, SunSpec Modbus TCP, JSON / SunSpec Modbus RTU
6 inputs and 4 digital I/Os OptionalLoad management; signaling, multipurpose I/OLoad management; signaling, multipurpose I/O

TYPE22.7-3 48024.0-3 480
Input (DC)
Max. permitted PV power34.09 kW36.00 kW
Max. usable input current (MPPT 1/MPPT 2)33.0 A / 25.0 A33.0 A / 25.0 A
Max. usable input current total (MPPT 1 + MPPT 2)51 A51 A
Max. admissible input current (MPPT 1/MPPT 2)49.5 A / 37.5 A49.5 A / 37.5 A
Max. admissible input current total (MPPT 1 + MPPT 276.5 A76.5 A
Integrated DC string fuse holders
Must be specified when ordering
Optional: 6- and 6+Optional: 6- and 6+
MPP voltage range500 – 800 V500 – 800 V
Operating voltage range200 – 1,000 V200 – 1,000 V
Max. input voltage1,000 V1,000 V
Nominal input voltage 208 VN/AN/A
240 VN/AN/A
480 V720 V720 V
Admissible conductor size DCAWG 14 – AWG 6 copper direct, AWG 6 aluminium direct, AWG 4 copper or aluminium with input combinerAWG 14 – AWG 6 copper direct, AWG 6 aluminium direct, AWG 4 copper or aluminium with input combiner
Number of MPPT22
OUTPUT DATA
Max. output power 208 VN/AN/A
240 VN/AN/A
480 V22,727 VA23,995 VA
Max. output fault current / Duration30.9 A RMS / 150.4 ms30.9 A RMS / 150.4 ms
Max. continuous output current 208 VN/AN/A
240 VN/AN/A
480 V27.3 A28.9 A
Recommended OCPD/AC breaker size 208 VN/AN/A
240 VN/AN/A
480 V35 A40 A
Max. efficiency98.00%98.00%
CEC efficiency 208 VN/AN/A
240 VN/AN/A
480 V97.50%97.50%
Admissible conductor size ACAWG 14 – AWG 6AWG 14 – AWG 6
Grid connection480 V Delta +N**480 V Delta +N**
Frequency60 Hz60 Hz
Total harmonic distortion< 1.75 %< 1.75 %
Power factor0 – 1 ind./cap.0 – 1 ind./cap.
GENERAL DATASTANDARD WITH ALL FRONIUS SYMO MODELSSTANDARD WITH ALL FRONIUS SYMO MODELS
Dimensions (width x height x depth)20.1 x 28.5 x 8.9 in. / 51.1 x 72.4 x 22.6 cm20.1 x 28.5 x 8.9 in. / 51.1 x 72.4 x 22.6 cm
Degree of protectionNEMA 4XNEMA 4X
Night time consumption< 1 W< 1 W
Inverter topologyTransformerlessTransformerless
CoolingVariable speed fanVariable speed fan
InstallationIndoor and outdoor installationIndoor and outdoor installation
Ambient operating temperature range-40 F to 140 F (-40 to 60 C)-40 F to 140 F (-40 to 60 C)
Permitted humidity0 – 100 % (non-condensing)0 – 100 % (non-condensing)
DC connection terminals6 x DC+ and 6 x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminum (solid / stranded)6 x DC+ and 6 x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminum (solid / stranded)
AC connection terminalsScrew terminals 14-6 AWGScrew terminals 14-6 AWG
Certificates and compliance with standards
(Except Symo 15.0 208 V)
UL 1741-2010, UL1998 (for functions: AFCI and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2008, ANSI/IEEE C62.41,
FCC Part 15 A & B, NEC Article 690, C22. 2 No. 107.1-01 ( September 2001), UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
UL 1741-2010, UL1998 (for functions: AFCI and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2008, ANSI/IEEE C62.41,
FCC Part 15 A & B, NEC Article 690, C22. 2 No. 107.1-01 ( September 2001), UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
Certificates and compliance with standards
(Symo 15.0 208 V)
UL 1741-2015, UL1998 (for functions: AFCI, RCMU and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2003, ANSI/IEEE C62.41,
FCC Part 15 A & B, NEC 2014 Article 690, C22. 2 No. 107.1-01 (September 2001) , UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
UL 1741-2015, UL1998 (for functions: AFCI, RCMU and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2003, ANSI/IEEE C62.41,
FCC Part 15 A & B, NEC 2014 Article 690, C22. 2 No. 107.1-01 (September 2001) , UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
PROTECTIVE DEVICESSTANDARD WITH ALL FRONIUS SYMO MODELSSTANDARD WITH ALL FRONIUS SYMO MODELS
AFCI & 2014 NEC CompliantYesYes
DC disconnectYesYes
DC reverse polarity protectionYesYes
Ground Fault Protection with Isolation
Monitor Interrupter
YesYes
INTERFACES /AVAILABILITYAVAILABLE WITH ALL FRONIUS SYMO MODELSAVAILABLE WITH ALL FRONIUS SYMO MODELS
USB (A socket) StandardDatalogging and inverter update via USBDatalogging and inverter update via USB
2 x RS422 (RJ45 socket) StandardFronius Solar Net, interface protocolFronius Solar Net, interface protocol
Wi-Fi/Ethernet/Serial/ Datalogger and
webserver Optional
Wireless standard 802.11 b/g/n / Fronius Solar.web, SunSpec Modbus TCP, JSON / SunSpec Modbus RTUWireless standard 802.11 b/g/n / Fronius Solar.web, SunSpec Modbus TCP, JSON / SunSpec Modbus RTU
6 inputs and 4 digital I/Os OptionalLoad management; signaling, multipurpose I/OLoad management; signaling, multipurpose I/O

updating…

Solar Energy

updating…

Additional information

Manufacturer

Fronius

You've just added this product to the cart: