Inverter 33KW Energy ABB
- Description
- Additional information
Description
HIGHLIGHTS
Updating..
| Input (DC) | PRO-33.0-TL-OUTD |
| Absolute maximum DC input voltage (Vmax,abs) | 1100 V |
| Start-up DC input voltage (Vstart) | 610 V |
| Operating DC input voltage range (Vdcmin…Vdcmax) | 580 to 950 V |
| Rated DC input voltage (Vdcr) | 580 V |
| Rated DC input power (Pdcr) | 33 700 W |
| Number of independent MPPT | 1 |
| MPPT input DC voltage range (VMPPTmin…VMPPTmax) at Pacr | 580 to 850 V |
| Maximum DC input current (Idcmax)/for each MPPT (IMPPTmax) | 58 A |
| Maximum input short circuit current for each MPPT | 80 A |
| Number of DC inputs pairs for each MPPT | 1 in standard and -S version/8 in -SX version |
| DC connection type | Tool-less PV connector Phoenix Sunclix on -SX version/screw terminal block on standard and -S version |
| Input protection | |
| Reverse polarity protection | Inverter protection only, from limited current source, via short-circuit diode and for fused -SX model when more than 2 strings are connected. |
| Input over voltage protection for each MPPT – varistor (-/S) version | 3 |
| Input over voltage protection – plug in modular surge arrester (-SX version) | 3 (Class II) |
| Photovoltaic array isolation control | According to local standard |
| DC switch rating for each MPPT (version with DC switch | 58 A/1000 V, 50 A/1200 V |
| Fuse rating (versions with fuses ) | 15 A/1100 V |
| Output side | |
| AC grid connection type | Three phase 3W or 4W+PE |
| Rated AC power (Pacr @cosφ>0.99 ) | 33 000 W |
| Maximum apparent power (Smax) | 33 000 VA |
| Rated AC grid voltage (Vac,r) | 400 V |
| AC voltage range | 320 to 480 V |
| Maximum AC output current (Iac,max) | 50.3 A |
| Contributory fault current | 50.3 A |
| Rated output frequency (fr) | 50 Hz / 60 Hz |
| Output frequency range (fmin…fmax) | 47…53 Hz / 57…63 Hz |
| Nominal power factor and adjustable range | > 0.995, with Pacr = 33.0 kW, adj. ± 0.9 with Pacr =29.7 kW, adj. ± 0 to 1 with S = 33.0 kVA |
| Total current harmonic distortion | < 3% |
| AC connection type | Fixed plug type connector |
| Output protection | |
| Anti-islanding protection | According to local standard |
| Maximum AC overcurrent protection | 50.3 A |
| Output overvoltage protection – varistor | 5 |
| Operating performance | |
| Maximum efficiency (ηmax) | 98.30% |
| Maximum efficiency (ηmax) | 98.0%/98.1% |
| Feed in power threshold | < 1 W |
| Stand-by consumption | < 20 W |
| Communication | |
| Remote monitoring | VSN700 Data logger (opt.) |
| User interface | Detachable graphical display |
| Environmental | |
| Ambient temperature range | -25 to +60°C /-13 to 140°F with derating above 45°C/113°F |
| Relative humidity | 0…100% condensing |
| Noise emission | < 67 dB(A) @ 1 m |
| Maximum operating altitude without derating | 2000 m / 6560 ft |
| Physical | |
| Environmental protection rating | IP 65 (IP54 fans) |
| Cooling | Forced |
| Dimension (H x W x D) | 740 x 520 x 300 mm/29.1″ x 20.5″ x 11.8 |
| Weight | < 66.0 kg/146 lb (standard version) |
| Mounting system | Wall bracket |
| Safety | |
| Isolation level | Transformerless |
| Marking | CE, RCM mark |
| Safety and EMC standard | EN 62109-1, EN 62109-2, EN 61000-6-2, EN 61000-6-3, EN 61000-3-11, EN 61000-3-12 |
| Grid standard (check your sales channel for availability) | CEI 0-21, CEI 0-16, VDE 0126-1-1, VDE-AR-N 4105, G59/3, VDE 0126-1-1/A1 VFR2014, PPC Greece, MEA, PEA, IEC 61727, IEC 62116, EN 50438, AS4777/AS3100, RD1699/RD661 (check from sales for additional grid standards) |
| Available products variants | |
| Standard | PRO-33.0-TL-OUTD-400 |
| With DC switch | PRO-33.0-TL-OUTD-S-400 |
| With DC+AC switch, fuse and surge arrester | PRO-33.0-TL-OUTD-SX-400 |
updating…
Solar Energy
updating…
updating…
Additional information
| Manufacturer | ABB |
|---|---|
| Origin | Italy |